Recent project · Moggill QLD 4070

Failed RPZ valve replaced

We replaced a failed RPZ valve at a Moggill community centre, and found the water pressure was 850 kPa, well above the 500 kPa maximum.

Service
Replacement lead-free 15mm RPZ valve
Location
Community centre, Moggill QLD 4070
Issue
Failed RPZ valve
Finding
Water pressure of 850 kPa, against a 500 kPa maximum
Lead-free 15mm RPZ backflow valve with blue ball valves and strainer installed on a brick wall at a Moggill community centreReplacement RPZ valve assembly, Moggill community centre.
What we found and did

A failed RPZ valve and pressure well over the limit

An RPZ (reduced pressure zone) valve protects the water supply from backflow. This one had failed at a community centre in Moggill. While we were on site, we measured the water pressure.

  • The issue. A failed RPZ valve.
  • What we found. Water pressure of 850 kPa, well above the proposed 500 kPa maximum for the building’s general supply.
  • New valve installed. A replacement lead-free 15mm RPZ valve, adjacent to the equipment it protects.
  • Recommendation made. A pressure reducing valve to limit downstream static pressure to 500 kPa.
Call 0401 666 855
How it went

Four steps from failed valve to a fix

What we measured, replaced and recommended.

  1. Measure the pressure

    During the works, the water pressure was measured at 850 kPa.

  2. Compare to the limit

    That is well above the proposed 500 kPa maximum for the building’s general water supply, and could have contributed to the RPZ valve failing.

  3. Replace the RPZ valve

    A replacement lead-free 15mm RPZ valve was supplied and installed, connected to the existing pipework for zone protection of the equipment.

  4. Recommend a PRV

    We recommended a suitably sized pressure reducing valve on the supply, set to limit downstream static pressure to 500 kPa.

Our recommendation

Protecting the new valve from high pressure

At 850 kPa, the supply was running well above the proposed 500 kPa maximum, which could have contributed to the failure. We recommended a suitably sized pressure reducing valve (PRV) on the community centre’s water supply, set to limit downstream static pressure to a maximum of 500 kPa.

Customer reviews

Don’t just take our word for it

Real reviews from Brisbane west homeowners, straight from Google.

Meet the team

The Asflow crew behind the work

Asflow Plumbing is a local, licensed team covering plumbing, gas fitting and drainage across Brisbane’s west. Need backflow prevention or pressure control sorted? We’ll assess it and fix it properly.

See more recent work
The Asflow Plumbing team standing beside their branded service trucks

Need an RPZ valve replaced?

Talk to a licensed Asflow plumber about RPZ valves, backflow prevention and water pressure problems. Quotes are quick and friendly.